Abstract
As an industrial customer of the utility, electrical arc furnace (EAF) is the major flicker source that degrades the grid power quality. As a possible solution, STATCOMs with high bandwidth can be used. In this paper, the normalized model of a CMC-based STATCOM and an EAF model are introduced, and then a DQ-model based control strategy is proposed for flicker mitigation. Case studies are conducted for STATCOM applying to a 40 MVA EAF arc furnace. Simulation results verify the controllers' stability and performance. A transient network analyzer (TNA) is developed to experimentally test the developed controller.