Abstract
An EHV power cable with compressed pure SF6 gas insulation was produced experimentally, and succeeded in the dielectric withstand test. The outside diameter of one phase of the cable was 14 inches. The conductor, composed of a metal pipe 4½ inches in diameter, was arranged at the center of the outer pipe, and supported by spacers placed at intervals of about 15 feet.

This publication has 4 references indexed in Scilit: