Effect of supply voltage harmonics on the input current of single-phase diode bridge rectifier loads
- 1 July 1995
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 10 (3), 1416-1422
- https://doi.org/10.1109/61.400924
Abstract
This paper describes the effect of supply voltage harmonics on the response of single-phase capacitor-filtered diode bridge rectifier loads. A complete analytical model for calculating the current harmonics of these loads, when energized by nonsinusoidal supply voltages, is presented. The model is then used to investigate the effect of supply voltage harmonics on current harmonics. The key findings of the paper are as follows: (1) the phase angles of supply voltage harmonics determine whether or not these harmonics increase or decrease current distortion. In general, a peaked voltage wave increases input current distortion, whereas a flattened wave has the opposite effect. Because of this complex relationship, voltage crest factor is a much better predictor of total harmonic current distortion than is total harmonic voltage distortion. (2) The current harmonics created by these loads produce voltage harmonics that tend to have a partial self-compensating effect on the current harmonics.Keywords
This publication has 3 references indexed in Scilit:
- Estimating Future Harmonic Distortion Levels In Distribution Systems Due To Single-Phase Adjustable-Speed-Drive Air Conditioners: A Case StudyPublished by Institute of Electrical and Electronics Engineers (IEEE) ,2005
- Power Supply Harmonic Limitation And Limits In Germany - Discussion And PracticePublished by Institute of Electrical and Electronics Engineers (IEEE) ,2005
- The harmonic impact of variable speed air conditioners on residential power distributionPublished by Institute of Electrical and Electronics Engineers (IEEE) ,2003