Removal of Radium‐226 From Sarasota County, Fla., Drinking Water by Reverse Osmosis
- 1 April 1980
- journal article
- research article
- Published by Wiley in Journal AWWA
- Vol. 72 (4), 230-237
- https://doi.org/10.1002/j.1551-8833.1980.tb04501.x
Abstract
Eight reverse osmosis treatment systems were used in Sarasota County (Fla.) for the removal of Ra‐226 and other dissolved solids from water. Although the age, type, and performance of the eight systems varied, all systems lowered the Ra‐226 concentration in the raw water to below the EPA maximum contaminant level of 5 pCi/L.This publication has 3 references indexed in Scilit:
- The Efficiency of Water Treatment Processes in Radium RemovalJournal AWWA, 1978
- Radium‐Removal Efficiencies in Water‐Treatment ProcessesJournal AWWA, 1978
- Greenfield, Iowa, Reverse Osmosis Desalting PlantJournal AWWA, 1972