Preliminary evaluation of a qualitative model-based fault detector for a central air-handling unit
- 1 January 1994
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 1873-1882 vol.3
- https://doi.org/10.1109/cca.1994.381249
Abstract
The feasibility of a qualitative approach for detecting faults in an air-conditioning system is considered. The system considered is a multi-zone variable air volume air-handling unit, and the faults investigated include types which result in deterioration of operation as distinct from actual failure. The operating modes of the sequential controller for the central air-handling plant can be matched to a corresponding qualitative classification of steady-state temperatures. Observed mismatches indicate the presence of faults. First trials of the method in an air-conditioning test laboratory are reported.Keywords
This publication has 3 references indexed in Scilit:
- Diagnosing multiple faultsArtificial Intelligence, 1987
- Qualitative simulationArtificial Intelligence, 1986
- Commonsense reasoning about causality: Deriving behavior from structureArtificial Intelligence, 1984