An algorithm for partial discharge location in distribution power transformers
- 7 November 2002
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- Vol. 3, 2217-2222
- https://doi.org/10.1109/pesw.2000.847700
Abstract
Partial discharges (PDs) are a major source of insulation failure in power transformers. Techniques for locating a PD source are of major importance in both the maintenance and repair of a transformer. A technique is described for locating a PD in a distribution power transformer. To study the propagation characteristics of a PD, a simulation model was developed for the transformer winding and the PD pulse. The terminal signals caused by PDs at different locations were analysed and the features related to the location extracted. An algorithm using feature template matching was developed for locating the PD source. Experimental tests carried out on a 110 kV continuous disc-type winding have verified the validity of the location algorithm. Results indicate that a location accuracy better than 5% of the winding length is normally achieved.Keywords
This publication has 4 references indexed in Scilit:
- A simulation model for propagation of partial discharge pulses in transformersPublished by Institute of Electrical and Electronics Engineers (IEEE) ,2002
- Detection and location of internal defects in the insulation of power transformersIEEE Transactions on Electrical Insulation, 1993
- Application of digital filtering techniques to the determination of partial discharge location in transformersIEEE Transactions on Electrical Insulation, 1989
- A Commentary on Partial Discharge Measurement and DetectionIEEE Transactions on Electrical Insulation, 1987