Transmission line fault location for phase-to-earth fault using one-terminal data
- 1 January 1999
- journal article
- Published by Institution of Engineering and Technology (IET) in IEE Proceedings - Generation, Transmission and Distribution
- Vol. 146 (2), 121-124
- https://doi.org/10.1049/ip-gtd:19990174
Abstract
An accurate algorithm for fault location of a single phase-to-earth fault on a two-parallel transmission line is presented. The faulted phase circuit and the zero-sequence circuit of the two-parallel line are used as a fault location model, in which the source impedance of the remote end is not involved. The algorithm effectively eliminates the effect of load flow and fault resistance on the accuracy of fault location. It embodies an accurate fault location by measuring only local data and is used in a procedure that provides the automatic determination of faulted types and phases, rather than requiring an engineer to specify them. Simulation results have demonstrated the validity of the algorithm under the condition of a phase-to-earth fault.Keywords
This publication has 5 references indexed in Scilit:
- Transmission line fault location for single-phase-to-earth fault on non-direct-ground neutral systemIEEE Transactions on Power Delivery, 1998
- Automated transmission line fault analysis using synchronized sampling at two endsIEEE Transactions on Power Systems, 1996
- Unsynchronized two-terminal fault location estimationIEEE Transactions on Power Delivery, 1996
- Transmission line fault location using digital fault recordersIEEE Transactions on Power Delivery, 1988
- Development of a New Type Fault Locator Using the One-Terminal Voltage and Current DataIEEE Transactions on Power Apparatus and Systems, 1982